SRW-TEC-004-10: Segmental Retaining Wall Design

Concrete Masonry & Hardscapes Association (CMHA, formerly NCMA and ICPI)

Open the source
Consulted
October 10, 2026
Region
US
Language
en

Cited by

What we take from it

  • CMHA recommends an engineered design above 1.2 m total height where the local code is silent.
  • CMHA calls for at least 300 mm of drainage stone behind the units, a drain of at least 75 mm and outlets at most 15 m apart.
  • CMHA sets the minimum length at the greater of 0.6 H and 1.2 m and a maximum vertical spacing between layers.
  • CMHA requires the wall drain to discharge at outlets.
  • CMHA calls for at least 300 mm of drainage stone behind the units.
  • CMHA spaces drain outlets no more than 15 m apart.
  • CMHA sets the minimum geogrid length at the greater of 0.6 H and 1.2 m.
  • CMHA recommends an engineered design above 1.2 m total height if the local code is silent.
  • Drainage, geogrid length and the 1.2 m threshold.